| | PQ5000MOBCLM (MULTI-PQ) | PQ5000MOBCL |
| Voltage connections | 5 | 5 |
| Number of Current Link modules | up to 9 | up to 9 |
| Current channels per Current Module | up to 36 | up to 36 |
| Function class acc. IEC 61000-4-30 | Class A | Class A |
| Device type acc. IEC 62586-1 | PQI-A FI1 | PQI-A FI1 |
| PQ COMPLIANCE MONITORING | voltages and currents | voltages only |
| Power frequency | ○ | ○ |
| Magnitude variations | ○ | ○ |
| Unbalance | ○ | ○ |
| THDS of voltages | ○ | ○ |
| Harmonics | ○ | ○ |
| Flicker Pst / Plt | ○ | ○ |
| Mains signalling voltages | ○ | ○ |
| Interharmonics voltage / current | ○ | ○ |
| PQ EVENT RECORDING | RMS 1/2 V + I and waveform U | RMS 1/2 V and waveform U |
| Voltage dip | ○ | ○ |
| Voltage interruption | ○ | ○ |
| Voltage swell | ○ | ○ |
| Rapid voltage change (RVC) | ○ | ○ |
| Current swell | ○ | - |
| Frequency anomaly | ○ | ○ |
| Ripple control sequences | RMS 1/2 U | RMS 1/2 U |
| MEASUREMENT UNCERTAINTY | | |
| Voltage | ±0,1% | ±0,1% |
| Current Current Module 3P/3PN | ±0,5% | ±0,5% |
| Power Current Module 3P/3PN | ±2.0% (typically) | ±2.0% (typically) |
| Active energy Current Module 3P/3PN | Class 3 (typically) | Class 3 (typically) |
| COMMUNICATION | | |
| Ethernet: Webserver, NTP | ○ | ○ |
| POWER SUPPLY | 100…230V AC | 100…230V AC |
| Consumption | ≤ 60VA | ≤ 60VA |
| DESIGN | | |
| Dimensions base unit | 360 x 304 x 194mm | 360 x 304 x 194m |